Cooling Capacity: |
3.5KW-9KW |
Color: |
Black/Grey White/other Custom Colors |
Mounting: |
Rack Mountnting |
Power: |
1N-220V-50Hz,110v/50hz/60hz |
Air Flow: |
750-1100M3/H |
Application: |
Cabinet/ Intelligent Project And Medium & Small Sized Enterprise |
Height: |
5U,9U |
Type: |
Split |
Voltage: |
220V, 380V |
Cooling Capacity: |
3.5KW-9KW |
Color: |
Black/Grey White/other Custom Colors |
Mounting: |
Rack Mountnting |
Power: |
1N-220V-50Hz,110v/50hz/60hz |
Air Flow: |
750-1100M3/H |
Application: |
Cabinet/ Intelligent Project And Medium & Small Sized Enterprise |
Height: |
5U,9U |
Type: |
Split |
Voltage: |
220V, 380V |
Horizontal Air-Cooled Rack-Mounted Air Conditioners Units Range From 4,000 BTU To Dual 20,000 BTU Configurations
Product Introduction COOL RACK Series rack-mounted air conditioner is a cabinet-level temperature control product specially designed for integrated cabinets data center, modular data center or high heat density data centers. It can be placed in the cabinet close to the heat source and can accurately handle the output of the equipment in the cabinet. The high sensible heat can effectively prevent the generation of local hot spots, reduce the return air distance, increase the return air temperature, and improve the energy efficiency ratio.
Applications
|
Advantages
High-level Configuration ▪ High-efficiency inverter compressor, ultra-precise PID control, more precise temperature control. ▪The well-known EC centrifugal fan can adjust the air volume output ratio in real time as needed. ▪Equipped with electronic expansion valve, smoothly adjust the throttle opening, realize precise adjustment of the unit. ▪Outdoor motor chopper speed regulation, which can realize 25-100% wide voltage speed regulation control. ▪R410A environmentally friendly refrigerant design. Safe & Reliable ▪Very wide grid adaptability, can meet ±20% voltage range, adapt to various harsh grid environments. ▪Multi-drainage and anti-back flow design to prevent cabinet flooding. ▪Intelligent self-detection of refrigerant capacity and intelligent early warning to ensure the safe operation of the refrigeration system. High Intelligent ▪High-efficiency inverter compressor, ultra-precise PID control technology. ▪Unique vibration compensation algorithm to realize broadband operation of the unit. ▪Safe and reliable anti-condensation algorithm to ensure the safe operation of the server. Easy Installation & Maintenance ▪Standard modular design to fit into standard server racks. ▪The design of plug-in terminals on the fan side and the whole machine makes the whole machine easy to maintain and fast to install; it occupies a small area and has 100% full frontal maintenance. ▪Refrigeration piping is connected with quick couplings. Various Options ▪Strong drainage of condensate ▪Wet film humidifier ▪Electric heater |
Air Supply Method
Indoor Unit Parameters
Model-CJA | 0003 | 0005 | 0007 | 0012 | |||
Phase/Function | 1.5P,Single Phase | 2P,Single Phase | 3P,Single Phase | 5P,Single Phase | |||
Parameters | |||||||
Cooling capacity kW | 3.5 | 5 | 7.5 | 12.5 | |||
Sensible cooling capacity k | W 3.5 | 5 | 7.5 | 12.5 | |||
Air volume m³/h | 800 | 1150 | 1600 | 2300 | |||
Sensible heat ratio % | 100 | 100 | 100 | 100 | |||
Heating kW (Option) | 1 | 1 | 2 | 3 | |||
Maximum operating current A | 15 | 15 | 25 | 34 | |||
Power Cord Cable Specifications | mm 3×2.5 | 3×2.5 | 3×4 | 3×6 | |||
Indoor/outdoor unit shut-off valve | |||||||
Refrigerant gas pipe φ mm | 12.7 | 12.7 | 12.7 | 15.88 | |||
Refrigerant liquid pipe φ mm | 9.52 | 9.52 | 9.52 | 9.52 | |||
Indoor unit structural parameters | |||||||
Dimension:W×D×H mm | 442×714×175 (4U) 442×714×218 (5U) |
442×714×218 (5U) | 442×714×351 (8U) | 442×714×440 (10U) | |||
Outdoor Unit | |||||||
Type-CJT | 3005 | 3005 | 3008 | 3013 | |||
Quantity | 1 | 1 | 1 | 1 |
Outdoor Unit Parameters
Type- CJT | 3005 | 3005 | 3008 | 3013 | |||
Power supply | 220Vac/1Ph/50Hz | ||||||
Installation | Vertical | ||||||
Speed mode | Stepless speed regulation | ||||||
Noise dBA | 54 | 55 | 56 | 58 | |||
Rated current A | 6 | 6 | 10 | 15 | |||
Power Cord Cable Specifications | mm 4×1.5 | 4×1.5 | 4×2.5 | 4×4 | |||
Communication cable specificati mm (with shielding function) | on 3×1 | 3×1 | 3×1 | 3×1 | |||
Structural parameters of outdoor unit | |||||||
Dimension:W×D×H mm | 840×285×610 | 840×285×610 | 880×360×800 | 930×390×1270 |
① The power cord of the outdoor unit must be connected from the indoor unit;
Certificates
Factory Details
Packing & Delivery
Cases